Fact Field Value Latest Entry Date
d55f6901d148124a0bd8f4a9eb48d43832b60c70275ee0c018098fce1a5295cc description Any liquid storage tanks should be located within a bund with a capacity of not less than 110% of the largest tank or largest combined volume of connected tanks. The drainage system of the bund shall be sealed with no discharge to any watercourse, land or underground strata. Associated pipe work shall be located above ground and protected from accidental damage. All filling points and tank overflow outlets shall be constructed to discharge vertically downwards within the bunded compound. 2025-06-21